Firmware History
v12b
- modified default custom settings float enter value to 30% (factory default value)
- fixed a MODBUS timing isse
v11
not released
v10b
firmware fix, corrected issue where firmware upgrade overwrites Ah, KWhr counters
v10
fixed an issue with Modbus code (RS-232 comm) which caused a communication lock-up under some conditions.
v09
- Float transistion counter now begins at 30% duty cycle (was 15%). Easier for L16's and older batteries to transition to float stage.
- Added differing LED indications for Equalize initiated and Equalize canceled when using push button to start/stop equalize cycles Equalize Initiated: RYG - RYG - G - G Equalize Canceled: RYG - RYG - R - R
- Added EEPROM register that allows the user to select PWM or ON/OFF type regulation in Diversion Mode. This option already exists in Solar Charging Mode (DIP switch #8)
v08
- Revised diversion setpoints table:
Absorption (V) |
Float (V) |
T_float |
Equalize(V) |
T_eq(hr) |
EQ (days) |
T_max_eq(hrs) |
13.8 |
13.6 |
4 |
14.1 |
3 |
28 |
3 |
14.0 |
13.6 |
4 |
14.3 |
3 |
28 |
3 |
14.2 |
13.6 |
4 |
14.5 |
3 |
28 |
4 |
14.4 |
13.6 |
4 |
14.7 |
4 |
28 |
4 |
14.6 |
13.7 |
4 |
14.9 |
4 |
28 |
5 |
14.8 |
13.7 |
4 |
15.1 |
4 |
28 |
5 |
15.0 |
13.7 |
4 |
15.3 |
4 |
28 |
5 |
- added EEPROM variable to adjust PWM% for transition into float
- fixed bug in lighting mode where lights stay on all night the first night if reset after dark
v07
- This version firmware not released to public, see v08 for fixes since v06
v06
- Self diagnostics test for a MOSFET short condition extended from 10min to 1 hour to avoid false fault condtion "FET SHORT" v05
- fixed DN causing overcurent fault in TS60
v04
- Fixed temperature compensation scaling issue in 24 and 48V systems.